Zero and Span Adjustments (Analog Transmitters)
This graph shows how any given percentage of input should correspond to the same percentage of output, all the way from 0% to 100%.
Things become more complicated when the input and output axes are represented by units of measurement other than “percent.” Take for instance a pressure transmitter, a device designed to sense a fluid pressure and output an electronic signal corresponding to that pressure. Here is a graph for a pressure transmitter with an input range of 0 to 100 pounds per square inch (PSI) and an electronic output signal range of 4 to 20 milliamps (mA) electric current:
Although the graph is still linear, zero pressure does not equate to zero current. This is called a live zero, because the 0% point of measurement (0 PSI fluid pressure) corresponds to a non-zero (“live”) electronic signal. 0 PSI pressure may be the LRV (Lower Range Value) of the transmitter’s input, but the LRV of the transmitter’s output is 4 mA, not 0 mA.
Any linear, mathematical function may be expressed in “slope-intercept” equation form:
Where,
y = Vertical position on graph
x = Horizontal position on graph
m = Slope of line
b = Point of intersection between the line and the vertical (y) axis
This instrument’s calibration is no different. If we let x represent the input pressure in units of PSI and y represent the output current in units of milliamps, we may write an equation for this instrument as follows:
The relation of the slope-intercept line equation to an instrument’s zero and span adjustments reveals something about how those adjustments are actually achieved in any instrument. A “zero” adjustment is always achieved by adding or subtracting some quantity, just like the y-intercept term b adds or subtracts to the product mx. A “span” adjustment is always achieved by multiplying or dividing some quantity, just like the slope m forms a product with our input variable x.
Zero adjustments typically take one or more of the following forms in an instrument:
• Bias force (spring or mass force applied to a mechanism)
• Mechanical offset (adding or subtracting a certain amount of motion)
• Bias voltage (adding or subtracting a certain amount of potential)
Span adjustments typically take one of these forms:
• Fulcrum position for a lever (changing the force or motion multiplication)
• Amplifier gain (multiplying or dividing a voltage signal)
• Spring rate (changing the force per unit distance of stretch)
It should be noted that for most analog instruments, zero and span adjustments are interactive. That is, adjusting one has an effect on the other. Specifically, changes made to the span adjustment almost always alter the instrument’s zero point1. An instrument with interactive zero and span adjustments requires much more effort to accurately calibrate, as one must switch back and forth between the lower- and upper-range points repeatedly to adjust for accuracy.
1It is actually quite rare to find an instrument where a change to the zero adjustment affects the instrument’s span.
Click here to go to the next page, Damping Adjustments
Go Back to Lessons in Instrumentation Table of Contents

Related Articles
- Pneumatic Instrumentation - Analysis of Practical Pneumatic Instruments
- LRV and URV Settings, Digital Trim (Digital Transmitters)
- Calibration Procedures
- Typical Calibration Errors
- NIST Traceability and Instrument Turndown
- Practical Calibration Standards
- Instrument Calibration (Calibration versus Re-Ranging)
- Practical Calibration Standards - Temperature Standards
- Practical Calibration Standards - Flow Standards
- Practical Calibration Standards - Electrical standards
- Practical Calibration Standards - Analytical Standards
- Instrumentation and Control - Instrument System Models and Calibration