Instrumentation Documents - Instrumentation Identification Tags

Up until this point, we have explored various types of instrumentation diagram, each one making reference to different instruments by lettered identifiers such as TT (Temperature Transmitter), PDT (Pressure Differential Transmitter), or FV (Flow Valve), without formally defining all the letters used to identify instruments. Part of the ISA 5.1 standard does exactly this, which is what we will now investigate.

Each instrument within an instrumented facility should have its own unique identifying tag consisting of a series of letters describing that instrument’s function, as well as a number identifying the particular loop it belongs to. An optional numerical prefix typically designates the larger area of the facility in which the loop resides, and an optional alphabetical suffix designates multiple instances of instruments within one loop.

For example, if we were to see an instrument bearing the tag FC-135, we would know it was a flow controller (FC) for loop number 135. In a large manufacturing facility with multiple processing “unit” areas, a tag such as this might be preceded by another number designating the unit area. For example, our hypothetical flow controller might be labeled 12-FC-135 (flow controller for loop #135, located in unit 12). If this loop happened to contain multiple controllers, we would need to distinguish them from each other by the use of suffix letters appended to the loop number (e.g. 12-FC-135A, 12-FC-135B, 12-FC-135C).

Each and every instrument within a particular loop is first defined by the variable that loop seeks to sense or control, regardless of the physical construction of the instrument itself. Our hypothetical flow controller FC-135, for example, may be physically identical to the level controller in loop #72 (LC-72), or to the temperature controller in loop #288 (TC-288). What makes FC-135 a flow controller is the fact that the transmitter sensing the main process variable measures flow. Likewise, the identifying tag for every other instrument within that loop2 must begin with the letter “F” as well. This includes the final control element as well: in a level control loop, the transmitter is identified as an “LT” even if the actual sensing element works on pressure (because the variable that the loop strives to sense or control is actually level, even if indirectly sensed by pressure), the controller is identified as an “LC”, and the control valve throttling fluid flow is identified as an “LV”: every instrument in that level-controlling loop serves to help control level, and so its primary function is to be a “level” instrument.

2Exceptions do exist to this rule. For example, in a cascade or feedforward loop where multiple transmitters feed into one or more controllers, each transmitter is identified by the type of process variable it senses, and each controller’s identifying tag follows suit.

Valid letters recognized by the ISA for defining the primary process variable of an instrument within a loop are shown in the following table. Please note that the use of a modifier defines a unique variable: for example, a “PT” is a transmitter measuring pressure at a single point in a process, whereas a “PDT” is a transmitter measuring a pressure difference between two points in a process. Likewise, a “TC” is a controller controlling temperature, whereas a “TKC” is a controller controlling the rate-of-change of temperature:

 

Letter
Variable
Modifier
A Analytical (composition)  
B Burner or Combustion  
C User-defined  
D User-defined Differential
E Voltage  
F Flow Ratio or Fraction
G User-defined  
H  Hand (manual)  
I Current  
J Power Scan
K Time or Schedule Time rate-of-change
L Level  
M User-defined Momentary
N User-defined  
O User-defined  
P Pressure or Vacuum  
Q Quantity Time-Integral or Total
R Radiation  
S Speed or Frequency Safety
T Temperature  
U  Multi-function  
V Vibration  
W Weight or Force  
X Unclassified X-axis
Y Event, State, or Presence Y-axis
Z Position or Dimension Z-axis

 

A “user-defined” letter represents a non-standard variable used multiple times in an instrumentation system. For example, an engineer designing an instrument system for measuring and controlling the refractive index of a liquid might choose to use the letter “C” for this variable. Thus, a refractive-index transmitter would be designated “CT” and a control valve for the refractive index loop would be designated “CV”. The meaning of a user-defined variable need only be defined in one location (e.g. in a legend for the diagram).

An “unclassified” letter represents one or more non-standard variables, each used only once (or a very limited number of times) in an instrumentation system. The meaning of an unclassified variable is best described immediately near the instrument’s symbol rather than in a legend. Succeeding letters in an instrument tag describe the function that instrument performs relative to the process variable. For example, a “PT” is an instrument transmitting a signal representing pressure, while a “PI” is an indicator for pressure and a “PC” is a controller for pressure. Many instruments have multiple functions designated by multiple letters, such as a TRC (Temperature Recording Controller ). In such cases, the first function letter represents the “passive” function (usually provided to a human operator) while the second letter represents the “active” (automated) control function.

 

Letter Passive function Active function
Modifier
A Alarm    
B User-defined User-defined User-defined
C   Control  
E Element (sensing)    
G  Glass or Viewport    
H      High
I  Indicate    
K    Control station  
L  Light
   Low
M      Middle or Intermediate
N  User-defined  User-defined  User-defined
O  Orifice    
P  Test point    
R  Record    
S    Switch  
T    Transmit  
U  Multi-function Multi-function Multi-function
V    Valve, Damper, Louver  
W  Well    
X  Unclassified  Unclassified Unclassified
Y    Relay, Compute, Convert  
Z   Driver, Actuator, or

          unclassified

     final control element

 

 

 

• Click here for the front page of this Instrumentation Documents article

Click here for Process Flow Diagrams (PFDs)

• Click here for Process and Instrument diagrams (P&IDs)

• Click here for Loop diagrams (“loop sheets”)

Click here for SAMA diagrams

• Click here for Instrument and Process Equipment Symbols

 Go Back to Lessons in Instrumentation Table of Contents

Comments (0)Add Comment

Write comment

security code
Write the displayed characters


busy

Related Articles

Promotions

  • ...more

Disclaimer

Important: All images are copyrighted to their respective owners. All content cited is derived from their respective sources.

Contact us for information and your inquiries. IAMechatronics is open to link exchanges.

IAMechatronics Login